61
Table 7. Weights and Dimensions
UPS Extended Battery Module
Dimensions
(WxDxH)
43.2 × 60.7 × 8.9 cm
17.0
× 23.9× 3.5(2U)
43.2 × 60.7 × 8.9 cm
17.0
× 23.9× 3.5(2U)
Weights 37 kg (81.5 lb) 42.5 kg (93 lb)
Table 8. Environmental and Safety
120V Models 208V Models 230V Models
Operating Temperature 0°C to 40°C (32°F to 104°F)
Optimal battery performance: 25°C (77°F)
Storage Temperature 0°C to 25°C (32°F to 77°F)
Transit Temperature -25°C to 55°C (-13°F to 131°F)
Relative Humidity 5–95% noncondensing
Operating Altitude Up to 3,000 meters above sea level
Transit Altitude Up to 10,000 meters above sea level
Audible Noise Less than 45 dBA Normal mode, typical load
Less than 50 dBA Battery mode
Surge Suppression IEEE C62.41 Category B IEEE C62.41 Category B
IEC 61000-4-5
IEC 61000-4-5
Safety Conformance UL 1778, UL 497A
CSA C22.2, No. 107.1, 107.2
NOM-019-SCFI
UL 1778, UL 497A
NOM-019-SCFI
IEC 60950-1; EN 62040-1-1
IEC 60950-1; EN 62040-1-1
Agency Markings cULus, NOM-NYCE cULus, NOM-NYCE, CE,
TÜV-GS (G models only)
CE, TÜV-GS
EMC (Class A) FCC Part 15, ICES-003 FCC Part 15, ICES-003 EN 50091-2, IEC 62040-2