Hardwired U PS Installation
WARNING
Only qualified service personnel (such as a licensed electrician) shall perform the electrical
installation. Risk of electrical shock.
CAUTION
S For UPS models with hardwired outputs, overcurrent protection for the output AC
circuit(s) is to be provided by others.
S For UPS models with hardwired outputs, suitably rated disconnect switches for the
output AC circuit(s) are to b e provided by others.
NOTE Do not make unauthorized changes to the UPS; o therwise, damage may occur to
your equipment and void your warranty.
The Powerware 9125 hardwired models require a dedicated branch
circuit that meets the following requirements:
S 40A minimum circuit with short circuit and overcurrent protection
S 200–240 Vac
S Single-phase
S 50/60 Hz
S The breaker must be wall-mounted and be readily accessible to the
operator
S Flexible metal conduit (recommended for ease of service and
maintenance)