Powerware 6000 VA Power Supply User Manual


 
SPECIFICATIONS
EATON Powerware
®
9125 Two-in-One UPS (5000/6000 VA) User’s Guide S 164201513 Rev B
www.powerware.com
49
Table 8. Weights and Dimensions
UPS Extended Battery Module (EBM)
Dimensions
(WxDxH)
44.2 x 68.3 x 21.8 cm
17.4” x 26.9” x 8.6” (5U)
44.2x68.3x13cm
17.4” x 26.9” x 5.1” (3U)
Weights UPS Chassis: 35 kg (77 lb)
Internal Battery Trays (2): 27.4 kg (60.5 lb) each
Total UPS Weight: 89.8 kg (198 lb)
69.9 kg (154 lb)
Table 9. Battery
Configuration (20) 12V, 7.2 Ah internal batteries
EBM Configuration PW9125 240 EBM: (20) 12V, 9 Ah
Type Sealed, maintenance-free, valve-regulated, lead-acid
Charging Internal battery: less than 2 hours to 80% usable capacity at nominal line voltage after
full load discharge
External battery: no more than 15x discharge time to 90% usable capacity at nominal
line voltage after full load discharge
Monitoring Advanced monitoring for earlier failure detection and warning
Table 10. Battery Runtimes (in Minutes)
Load
UPS Internal
Batteries
1EBM 2EBMs 3EBMs 4EBMs
6000 VA/4200W 9.7 29.7 52.1 76.3 102
5000 VA/3500W 13.2 37.4 65.3 95.6 127.7
4000 VA/2800W 19.2 49.2 85.8 125.4 167.5
3000 VA/2100W 24.3 70.1 121.9 178.0 237.4
2000 VA/1400W 37.7 107.5 186.2 271.4 361.6
NOTE Battery times are approximate and vary depending on the load configuration and battery charge.