Powerware 6000 VA Power Supply User Manual


 
SPECIFICATIONS
EATON Powerware
®
9125 Two-in-One UPS (5000/6000 VA) User’s Guide S 164201513 Rev B
www.powerware.com
48
Table 6. Electrical Output
Regulation
(Normal Mode)
Nominal output voltage ±3%
Regulation
(Battery Mode)
Nominal output voltage ±3%
Voltage Waveform Normal mode: Sine wave; <3% THD with linear or PFC load;
<6% with nonlinear load or SMPS
Output Receptacles L6-30R or Hardwired
Table 7. Environmental and Safety
Operating Temperature 0°C to 40°C (32°F to 104°F)
Optimal battery performance: 25°C (77°F)
Storage Temperature 0°C to 25°C (32°F to 77°F)
Transit Temperature -25°C to 55°C (-13°F to 131°F)
Relative Humidity 5–95% noncondensing
Operating Altitude Up to 3,000 meters above sea level
Transit Altitude Up to 10,000 meters above sea level
Heat Dissipation 2066 BTU/hr maximum
Audible Noise Less than 50 dBA Normal mode, typical load
Less than 60 dBA Battery mode
Leakage Current < 0.6 mA
Communication DB-9: 1200-19200 baud; USB 1.1 compliant
Surge Suppression ANSI C62.41 Category B3
EN 61000-4-5 Level 3, Criteria B
Safety Conformance UL 1778;
CSA C22.2, No. 107.1, 107.2;
EN 50091-1-1 and IEC 60950;
NOM-019-SCFI
Agency Markings cULus, cUL, NOM-NYCE, CE
UL/DEMKO GS (hardwired models only)
EMC (Class A) EN 50091-2, FCC Part 15, ICES-003