Powerware 650825 kVA Power Supply User Manual


 
UPS OPERATING INSTRUCTIONS
EATON Powerware
®
9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com
7−22
8. On the System Status screen, select the UPM command.
9. On the UPS Control Command screen, select the
UPM 1 command.
10. Press the
CONTROLS pushbutton on the System Status menu bar. The UPM 1
Control Command screen is displayed.
11. On the UPM 1 Control Command screen, select UPM ON.
12. Press the
SELECT pushbutton on the UPM 1 Command menu bar.
13. Verify the following messages display sequentially on the UPM status line:
DC STARTING, CHARGER OFF
INVERTER STARTING
INVERTER SYNCING
READY
The UPM 1 rectifier and inverter turn on.
If the Inherent Redundancy option is enabled, a loss of redundancy alarm will be
issued. Silence the alarm and continue to Step 14.
14. Repeat Steps 8 through 12 selecting
UPM 2 to start UPM 2.
15. Observe the following messages are displayed sequentially on the
UPM status line:
DC STARTING, CHARGER OFF
INVERTER STARTING
INVERTER SYNCING
READY
The UPM 2 rectifier and inverter turn on.
16. Repeat Steps 8 through 12 selecting
UPM 3 to start UPM 3.
17. Verify the following messages display sequentially on the UPM status line:
DC STARTING, CHARGER OFF
INVERTER STARTING
INVERTER SYNCING
READY
The UPM 3 rectifier and inverter turn on. When the inverter reaches full voltage,
the UPS is ready to transfer to the Normal mode and supply the critical load.
18. If the UPS is a Plus 1 model, repeat Steps 8 through 12 selecting
UPM 4 to start
UPM 4.
19. Verify the following messages display sequentially on the UPM status line:
DC STARTING, CHARGER OFF
INVERTER STARTING
INVERTER SYNCING
READY
The UPM 4 rectifier and inverter turn on. When the inverter reaches full voltage,
the UPS is ready to transfer to the Normal mode and supply the critical load.