Powerware 650825 kVA Power Supply User Manual


 
EATON Powerware
®
9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com
10−1
Chapter 10 Product Specifications
10.1 Model Numbers
The UPS is housed in a free-standing cabinet, divided into two sections with safety
shields behind the door and front panels. The UPS is available in 50 or 60 Hz with
various output power ratings.
Models Power Rating Frequency
Powerware 9395−825/650 650 kVA 50/60 Hz
Powerware 9395−825/750 750 kVA 50/60 Hz
Powerware 9395−825/825 825 kVA 50/60 Hz
The following sections detail the input, output, environmental, and battery
specifications for the UPS.
10.2 Specifications
10.2.1 UPS Input
Operating Input Voltage 400 Vac
480 Vac
Operating Input Frequency Range 50/60 Hz
Operating Input Current See Table 3-4 on page 3−9, Table 3-5 on page 3−10, or Table 3-6 on
page 3−11.
Reduced for Generator
Adjustable
Input Current Harmonic Content 5% THD at full load
Power Factor Minimum 0.99
Line Surges 6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801-4
Battery Voltage 480 Vdc
Battery Charging Capacity Configurable per UPM at nominal line voltage:
Up to 120A with less than 85% load
Up to 80A with 100% load
Battery Shunt Trip 48 Vdc
Figure 10Table 10