Powerware 650825 kVA Power Supply User Manual


 
UPS INSTALLATION PLAN AND UNPACKING
EATON Powerware
®
9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com
3−10
Table 3-5. Input/Output Ratings and External Wiring Requirements for the Powerware 9395−825/650, 9395−825/750, and 9395−825/825
– Separate Battery
Basic Unit Rating
Units Rating 50/60 Hz
kVA
kW
650
585
650
591
750
675
750
682
825
742
825
750
Input and Output Voltage Volts 400/400 480/480 400/400 480/480 400/400 480/480
AC Input to UPS Rectifier (0.98 Minimum pF)
Full load current plus battery recharge current
(3) Phases, (1) Ground
A
Amps 1079 891 1245 1028 1369 1130
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(4)
500
(3)
500
(4)
500
(4)
500
(5)
500
(4)
AC Input to UPS Bypass (Four Wire)
Full Load Current
(3) Phases, (1) Ground
B
Amps 938 782 1083 902 1191 992
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(3)
350
(3)
500
(4)
500
(3)
500
(4)
500
(4)
AC Input to UPS Bypass (Five Wire)
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
B
Amps 938 782 1083 902 1191 992
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
400
(4)
500
(3)
500
(5)
500
(4)
500
(5)
500
(5)
DC Input from Each Battery Disconnect to Each UPS
UPM
(1) Positive, (1) Negative
C
Amps per UPM 551 551 551 551 551 551
Minimum Conductor Size
Number per Pole
AWG or kcmil
(each)
250
(3)
250
(3)
250
(3)
250
(3)
250
(3)
250
(3)
AC Output to Critical Load (Four Wire)
Full Load Current
(3) Phases, (1) Ground
D
Amps 938 782 1083 902 1191 992
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(3)
350
(3)
500
(4)
500
(3)
500
(4)
500
(4)
AC Output to Critical Load (Five Wire)
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
D
Amps 938 782 1083 902 1191 992
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
400
(4)
350
(3)
500
(5)
500
(3)
500
(5)
500
(4)
Neutral Bonding Jumper (Four Wire Output Only)
Minimum Conductor Size
Number
AWG or kcmil
(each)
4/0
(1)
4/0
(1)
4/0
(1)
4/0
(1)
4/0
(1)
4/0
(1)
NOTE Callout letter A,maps to Figure 6-6, Figure 6-8, Figure 6-10, or Figure 6-12 starting on page 6−9. Callout letters B, C, and D map to Figure 6-6,
Figure 6-8, Figure 6-10, Figure 6-12, Figure 6-13, Figure 6-14, Figure 6-15, or Figure 6-16 starting on page 6−9.