Schneider Electric 174 CEV Network Router User Manual


 
Diagnostic Tools
72
6.15 Option 8: Token Owner Work Table
Figure 29 Token Owner Work Table
MODBUS PLUS NETWORK STATUS version 2.10
Node Token Owner Bit Map
Adapter: 1
Success: 208
Failure: 0
Information from node 30 (30.00.00.00.00)
1 2 3 4 5 6 7 8
1 Data-master token owner
Data-master get-master-response transfer request
Data-slave token owner
Data-slave get-slave-command transfer request
1 Program-master token owner
Program-master get-master-response trans request
Program-slave token owner
Program-slave get-slave-command transfer request
1 Program-master connect-status
Program-slave automatic logout request
2
This option continuously queries the specified node for its list of internal paths that
are active. The paths listed are the node’s internal data and program paths.
As a path goes active its number is listed in the columns to the left. Paths shown
in normal video are those remaining active during the test. Paths in reverse video
are those which were active at least once during the test, but which have
subsequently gone inactive.
The option runs continuously and displays a pass count until you terminate it by
pressing Escape.