Sharp JW-20CM Computer Hardware User Manual


 
13·17
•Use addresses 000001 to 000017(8) listed below when the I/Os are the JW type.
If ZW type I/Os are used, no setting is required.
(2) JW-20RS
Initial value of the address 000000 to 000017(8) are all 00(H).
000001
000002
000003
000004
000005
000006
000007
Set contents
Set number of dummy I/O points
Rack number: 0
D7 6543210
Slot: 3 Slot: 2
(Setting method is same as 000000(8).)
Address(8)
Slot: 5 Slot: 4
Slot: 7 Slot: 6
Slot: 9 Slot: 8
Slot: B Slot: A
Slot: D Slot: C
Slot: F Slot: E
000010
000011
000012
000013
000014
000015
000016
000017
Set contents
Set number of dummy I/O points
Rack number: 1
D7 6543210
Slot: 1 Slot: 0
(Setting method is same as 000000(8).)
Address(8)
Slot: 3 Slot: 2
Slot: 5 Slot: 4
Slot: 7 Slot: 6
Slot: 9 Slot: 8
Slot: B Slot: A
Slot: D Slot: C
Slot: F Slot: E
: Setting is necessary (1/2)
000000
Address(8)
Set contents Setting method (value)
00(H)
01(H)
02(H)
03(H)
04(H)
05(H)
06(H)
07(H)
08(H)
09(H)
0A(H)
0B(H)
0C(H)
0D(H)
0E(H)
0F(H)
Dummy I/O points is none
Dummy I/O points is 16 (2 bytes)
Dummy I/O points is 32 (4 bytes)
Dummy I/O points is 48 (6 bytes)
Dummy I/O points is 64 (8 bytes)
Dummy I/O points is 80 (10 bytes)
Dummy I/O points is 96 (12 bytes)
Dummy I/O points is 112 (14 bytes)
Dummy I/O points is 128 (16 bytes)
Dummy I/O points is 144 (18 bytes)
Dummy I/O points is 160 (20 bytes)
Dummy I/O points is 176 (22 bytes)
Dummy I/O points is 192 (24 bytes)
Dummy I/O points is 208 (26 bytes)
Dummy I/O points is 224 (28 bytes)
Dummy I/O points is 240 (30 bytes)
Set number of dummy I/O points
Rack number: 0
D7 6543210
Slot: 1 Slot: 0
Set vacant 2 slots
Set only in case of manual I/O table
registration
For address 000000(8), set 00(H)
JW-I/O