113
· Connection
The PV generator is connected by means of
the externally accessible, touch-safe Tyco
Solarlok connectors included in the con-
signment. The Tyco Solarlok connectors are
designed for a cable cross-section of 4 mm
2
and have to be crimped. For further infor-
mation, please read chapter 4.2 «Tyco
Solarlok Connectors».
Please note:
All PV generator inlets are positioned in
pairs. Inlet 1 is left, inlet 2 is in the middle,
and inlet 3 is right. The upper connections
are «POSITIVE», and the lower ones are
«NEGATIVE».
Illustr.: PV generator connection via Tyco
Solarlok connectors
Important Information
· The DC voltage can reach up to 850 V.
The device may only be opened by a
qualified electrician!
· As soon as the PV generator has been
connected to the Solar Inverter by means
of the DC connectors and the PV genera-
tor has been switched on, the PV genera-
tor voltage is applied internally!
· Please note that the inlet capacitors are
still live, even after the PV generator has
been switched off or the PV generator
connector has been pulled out!
· After the AC and DC sides have been
isolated, the Solar Inverter remains live
for up to approximately five minutes!
· Therefore, wait at least five minutes for
the internal voltage to discharge. Prior to
working on the Solar Inverter, always
!