8 Transporting
The UPS may be packed in a crate for extra protection during transportation. Avoid impact or vibration
against the UPS during transportation. DO NOT expose the UPS directly to water.
WARNING
When transporting the UPS by crane, follow the SPECIFIED WORK PROCEDURE.
The suspension wire angle should be less than 60°.
The UPS falling or overturning may cause crushing, trapping or other personal
injuries.
DO NOT tilt the UPS more than 10° from upright position.
Tilting the UPS more than 10° may cause crushing, trapping or other
personal injuries.
CAUTION
DO NOT transport, move, store, or place the UPS on its side.
Excessive force applied from heavy components inside may damage
the UPS.
Avoid vibration or shock exceeding 0.5G.
Failing to observe this precaution may cause damage to the UPS.
DO NOT allow the UPS to suffer shock or impact when
unpacking.
Tools used to remove packaging materials may cause damage to the
UPS.
DO NOT install the UPS where water may fall on it.
Water may cause electrical shock, personal injury or UPS failure.
DO NOT push or pull on the sides of the packaging.or the
UPS to move it. Always use a crane, forklift, or pallet jack for
transporting and positioning the UPS.
Pushing/pulling on the sides of the unit to move it may result in damage
to the UPS. (See Figure 4.1 Exterior Handling label.)