50
G8000 Series Installation and Operation Manual
G8000 Specications
Model Number
T80S3K08
KK6XSxx
T80S3K10
KK6XSxx
T80S3K12
KK6XSxx
T80S3K15
KK6Xxx
T80S3K22
KK6XSxx
T80S3K30
KK6XSxx
T80S3K50
KK6XSxx
Output
Voltage 480Y/277V
Conguration 3-Phase; 4-Wire + Gnd
Voltage
Regulation
±1% for 0-100%Balanced and Unbalanced Loads ±2% for
0-100%
Balanced
and Unbal-
anced Loads
Voltage Adjust-
ment Range
±5% (in increments of 1V)
Voltage
Unbalance
±3% for 100% Linear Loads ±5% for 100% Non-Linear Loads
Crest Factor 2
Transient Voltage
Response
±2% Max with a 100% Step Loads (without utilizing batteries)
±1.5% Max with Loss/Return AC input
±2% Max when load transfers To/From Bypass
Transient
Recovery Time
<50 ms
Frequency 60 Hz
Frequency Syn-
chronous Range
±0.5 Hz, ±1 Hz, + 1.5Hz (Selectable)
Frequency Slew
Rate
1 Hz/Sec
Frequency Regu-
lation
± 0.01% in free running mode
Current 96 A 120 A 150 A 180 A 271 A 361 A 601 A
Power Factor 1.0 PF Lag: 32 - 86 °F (0
- 30 °C)
0.8 PF Lag: 86 - 104 °F
(30 - 40 °C)
0.8 PF Lag:
32 - 104 °F
(0 - 40 °C)
1.0 PF Lag: 32 - 86 °F (0 - 30 °C)
0.8 PF Lag: 86 - 104 °F (30 - 40 °C)
0.9 PF
Lag
32 - 104 °F
(0 - 40 °C)
Overload
Capacity
125% for 10 Minutes,
150% for 60 Seconds
110% for
5 Minutes,
120% for
60 Seconds
125% for 10 Minutes, 150% for 60 Seconds
Voltage THD <3% Max with 100% Linear Load / 5% Max with 100% Non-Linear Load
Withstanding
Rating
65 kA (with optional fuse)
Reliabil-
ity
MTBF Module only - 200,000 Hrs. / 3,000,000 Hrs. in Bypass
Environ-
ment
Cooling Forced Air
Paint Color Sherwin Williams HHT2-7055, 079 Beige Texture
Weight 1740 lb.
(789 kg)
1740 lb.
(789 kg)
2467 lb.
(1119kg)
2980 lb.
(1352 kg)
4575 lb.
(2075 kg)
6520 lb.
(2957 kg)
Weight (Shipping) 1790 lb.
(812 kg)
1790 lb.
(812 kg)
2556 lb.
(1159 kg)
3069 lb.
(1392 kg)
4725 lb.
(2143 kg)
-TBD-
Floor Loading 210 Lbs/ft²
(1023 kg/m2)
210 Lbs/ft²
(1023 kg/m2)
203 Lbs/
ft² (990 kg/
m2)
245 Lbs/ft²
(1196 kg/
m2)
240 Lbs/ft²
(1173 kg/
m²)
247 Lbs/ft²
(1204 kg/m²)