74
G8000 Series Installation and Operation Manual
TABLE 15.5 - WARNING - 2 (STOP AND RESTART)
Item LCD Message Indication Description
27I
AC O/P UV AC output voltage is low.
30U UNIT FAULT IGBT Stack Failure.
45 DC OV Over-voltage in DC circuit.
49 AC O/P OL Output overload
51I
INV. OC Inverter over-current.
59I
AC O/P OV AC output voltage is high.
76C BATT. OC Over-current in Battery section.
TABLE 15.6 - WARNING (OPERATION CONTROL)
Item LCD Message Indication Description
27C BYPASS UV Bypass input voltage is low.
47C BYPASS ERR. Bypass input phase rotation error.
59C BYPASS OV Bypass input voltage is high.
95C BYPASS ASY. Bypass input frequency error.
TABLE 15.7 - WARNING (GUIDANCE)
Item LCD Message Indication Description
26B BATT. OVER HEAT Battery temperature is too high.
80B1 BATT. UV (ALM) Battery voltage is near cutoff voltage.