Toshiba 500 KW Power Supply User Manual


 
58
G8000 Series Installation and Operation Manual
TABLE 13.3 - CONTINUED
MEASUREMENT SCREENS
O/P CURRENT (PEAK)
Shows the peak output current peak (%) for each phase.
U 50[%]
V 50[%]
W 50[%]
Peak value of output current
x 100 [%]
RMS value for rated current x 1.41
AC INPUT
Shows the AC Input Voltage (line-to-line) and frequency.
AC I/P-V 480[V]
FREQ. 60.0[Hz]
BYPASS INPUT
Shows the Bypass Input Voltage (line-to-line voltage) and
frequency.
BYP I/P-V 480[V]
FREQ. 60.0[Hz]
DC INPUT
Shows the internal DC bus voltage, battery voltage and
battery current.
The battery current value displayed is negative during
recharge and positive during discharge.
DC-V 632[V]
BATT-V 400[V]
BATT- I 0[A]
MODE COUNT
Shows the cumulative UPS operation time, the
cumulative battery backup time and the number of battery
backup operations.
UPS 35[H]
BATTERY 56[MIN]
32[TIM]
CLOCK
The current time is displayed if there are no faults
recorded, or after the reset button is pressed.
Date is displayed in the mm-ddyyy format. The unit does
not calculate daylight savings time.
Time is displayed in the 24-hour format (e.g. 1:58 P.M. =
1358 Hrs.)
TIME 03-24-06 13:58