Toshiba 500 KW Power Supply User Manual


 
36
G8000 Series Installation and Operation Manual
See Table 11.5 – Table 11.6 for recommended cable sizes for the 150, 225, 300 and 500 kVA UPS.
TABLE 11.3 RECOMMENDED CRIMP TYPE COMPRESSION LUGS FOR BUS STRIP TERMINALS
Wire Size Wire
Strand
Class
Recommendation Crimp tool Required
Burndy type Y35 or Y46
Vendor Cat. No. Color Key Die Index
1/0 B
I
B
Burndy
Ilsco
Burndy
YA25
CRA-1/OL
YA25-LB
Pink
Pink
Black
12 / 348
12 / 348
13
2/0 B
I
B
Burndy
Ilsco
Burndy
YA26
CRA-2/OL
YA27-LB
Black
Black
Orange
13
13
14 / 101
3/0 B
I
B
Burndy
Ilsco
Burndy
YA-27
CRB-3/OL
YA28-LB
Orange
Orange
Purple
14 / 101
14 / 101
15
4/0 B
I
B
Burndy
Ilsco
Burndy
YA28
CRB-4/OL
YA29-LB
Purple
Purple
Yellow
15
15
16
300 MCM B
I
B
Burndy
Ilsco
Burndy
YA30
CRA-30OL
YA32-LB
White
White
Red
17 / 298
17 / 298
18 / 324
350 MCM B
I
Burndy
Ilsco
YA31L
CRA-350
Red
Red
18
18
600 MCM B
I
Burndy
Ilsco
YA36L
CRA-600
Green
Green
22
22
TABLE 11.4 RECOMMENDED CABLE SIZE AND FASTENER TORQUE FOR 150 KVA UNIT
(USE 75 °C Copper Wire)
Recommended external cable sizes for both 75 °C and 90 °C copper wire for minimum battery congurations
are listed in Table 11.4–11.7. For extended runtime battery strings congurations consult with Toshiba
Technical Support. Ensure that your installation adheres to local and NEC electrical codes.