Toshiba 500 KW Power Supply User Manual


 
23
G8000 Series Installation and Operation Manual
9 Storage/Operating Environment
Observe the following when storing the UPS.
• Store UPS indoors.
• Maximum storage time for the UPS between powered operation cycles is three years. If the UPS
has been stored for a period exceeding 36 months, contact your factory authorized represnetative
of guidance in starting the unit.
• Temperature uctuations should be minimized.
• The optimal storage temperature range is 68 – 77 °F (20 – 25° C).
• A maximum temperature range of 32 – 104 °F (0 – 40 °C) should be observed.
• The optimal relative humidity at the storage location should be between 50 – 60%.
• Humidity must not exceed 90%.
• Avoid locations where UPS may be exposed to corrosive gas.
• Avoid locations with dirt and/or dust.
TABLE 9.1 - UPS STORAGE/OPERATING ENVIRONMENT STANDARDS
Item Environment standard
Storage Location Indoors
Ambient Temperature
Minimum storage temperature: 32 °F (0 °C)
Maximum storage temperature: 104 °F (40 °C)
Relative Humidity
The relative humidity must be between 30 and 90% and without condensation
due to temperature changes.
Altitude
This equipment is rated for installations up to 3240 ft. (1000m) above
sea level. Consult with the factory to determine the derating factor for
installations above 3240 ft. (1000m).
Dust
Dust must not exceed normal atmospheric levels and must not include
conductive particles, silicone or oils.
Flammable Gas
No ammable and/or explosive gas.
Hydrogen sulde (H
2
S) Less than or equal to 0.0001 PPM
Sulfurous acid gas (SO
2
) Less than or equal to 0.05 PPM
Chlorine gas (Cl
2
) Less than or equal to 0.002 PPM
Ammonia gas (NH
3
) Less than or equal to 0.1 PPM
Nitrous acid gas (NO
2
) Less than or equal to 0.02 PPM
Nitrous oxides (NOx) Less than or equal to 0.02 PPM
Ozone (O
3
) Less than or equal to 0.002 PPM
Hydrochloric acid mist (HCl) Less than or equal to 0.1 mg/m
3
9.1 Operating Precautions
Initial startup/comisioning of the UPS should be performed by factory authorized personnel.
1) The UPS should not be powered up until the entire operation manual has been read.
2) The voltage of the input power source must be within the rated input voltage range. The