Toshiba T2N Network Card User Manual


 
146
6 F 3 B 0 3 6 2
8.3 T2N Special Relays and Registers
The Ethernet Port status information is reflected in the T2N special relays and special registers.
1. Special relays
Special relay Name Function
S000B Ethernet Port error
(warning)
1: The installed Ethernet Port unit is down.
(The T2N continues to operate.)
0: Reset the system from a user program after resolving the
error in the down Ethernet Port.
2. Special registers
Special registers Name
SW063 CH1 station status
3. Station status format
F E D C B A 9 8 7 6 5 4 3 2 1 0
Bit F: DOWN (down)...........................................1: Down mode, 0: Other than down mode
Bit E: INZ (initialization).....................................1: Initialization in progress
0: Initialization completed
Bit D: STBY (standby).........................................1: Standby mode
0: Other than standby mode
Bit C: RUN (run)..................................................1: Run mode, 0: Other than run mode
Bit 5: MTEN (Message transmission)..................1: Enabled, 0: Prohibited
Bit 4: STEN (socket interface transmission).........1: Enabled, 0: Prohibited
Bit 0: TEST (test).................................................1: Test function execution in progress
TESTMTENSTBYDOWN
STENRUNINZ