Toshiba T2N Network Card User Manual


 
58
6 F 3 B 0 3 6 2
For the T/C registers, the data length will be between 1 and 323 words.
(2) Local port register type code
This code indicates the type of register in which the local port transmission source data is
stored. See figure 5.1 for the codes that can be specified.
(3) Local port register number
Specifies the starting number of the register specified by the local port register type code.
(4) Remote port register type code
This code specifies the type of the register at the remote port to which the transmitted data will
be written. See figure 5.1 for the codes that can be specified.
(5) Remote port register number
Specifies the starting number of the register specified by the remote port register type code.
(6) Timer count
Specifies a time used to limit the response time from the remote port in 0.1 second units.
F E 0
A+10
Figure 5.1 indicates the register type code that the local or remote port can specify the code. See
T-series Instruction Set (Ladder, SFC) (UM-TS03***-E004).
RID Meaning RID Meaning
0000H XW/YW registers
∗∗05H
F register (0 - 8191)
*1
0001H W register
∗∗06H
F register (0 - 65535)
*2
0002H LW register 0007H T register
*3
0003H RW register 0008H C register
*3
0004H D register 0009H SW register
Figure 5.1 Register Type Code
*1 Includes the expansion F registers. One bank has 8k words (0 to 8191).
F 7 0
05H
0: Use the user-specified value (0.1 to 3276.7 seconds)
1: Use the default value of 30 seconds.
Bank number ...00H: T2N internal registers
F0000 to F1023
01H to 03H: Expansion F registers
F0000 to F8191