Western Telematic MPC-8H-1 Network Card User Manual


 
1-2
Introduction
Convenient, Durable Design:
The MPC is available with an optional remote display panel, which can be used to show
the status of MPC units installed in hard-to-reach spots, deep inside equipment racks.
When additional outlets are needed, each MPC unit can also be connected to up to
three Auxiliary/Remote MPC units, allowing control of up to 80 outlets via a single IP
Address .
Model Numbers
The MPC series includes a variety of horizontal and vertical models to accommodate the
power distribution needs of almost any rack mount application.
Model No.
Input
Feeds
Input
Voltage
Max. Load
per Outlet
Max. Load
per Input
Max. Load
per Unit
MPC-8H-1 2 ea, 20 Amp 100 to 120 VAC 16 Amps 16 Amps * 32 Amps *
MPC-8H-2
2 ea, 16 Amp 100 to 240 VAC 10 Amps 16 Amps * 32 Amps *
MPC-16H-1
2 ea, 20 Amp 100 to 120 VAC 16 Amps 16 Amps * 32 Amps *
MPC-16H-2
2 ea, 16 Amp 100 to 240 VAC 10 Amps 16 Amps * 32 Amps *
MPC-18H-1
1 ea, 20 Amp 100 to 120 VAC 16 Amps 16 Amps * 16 Amps *
MPC-18H-2
1 ea, 16 Amp 100 to 240 VAC 10 Amps 16 Amps * 16 Amps *
MPC-20V-1
2 ea, 20 Amp 100 to 120 VAC 16 Amps 16 Amps * 32 Amps *
MPC-20V-2
2 ea, 16 Amp 100 to 240 VAC 15 Amps 16 Amps * 32 Amps *
MPC-20VS20-1
1 ea, 20 Amp 100 to 120 VAC 16 Amps 16 Amps * 16 Amps *
MPC-20VS20-2
1 ea, 16 Amp 100 to 240 VAC 15 Amps 16 Amps * 16 Amps *
MPC-20VD20-1
2 ea, 20 Amp 100 to 120 VAC 16 Amps 16 Amps * 32 Amps *
MPC-20VD20-2
2 ea, 20 Amp 100 to 240 VAC 15 Amps 16 Amps * 32 Amps *
MPC-20VS30-1
1 ea, 30 Amp 100 to 120 VAC 20 Amps 24 Amps * 24 Amps *
MPC-20VS30-2
1 ea, 30 Amp 100 to 240 VAC 15 Amps 24 Amps * 24 Amps *
MPC-20VD30-1
2 ea, 30 Amp 100 to 120 VAC 20 Amps 24 Amps * 48 Amps *
MPC-20VD30-2
2 ea, 30 Amp 100 to 240 VAC 15 Amps 24 Amps * 48 Amps *
MPC-20VS16-3
1 ea, 16 Amp 100 to 240 VAC 10 Amps 16 Amps 16 Amps
MPC-20VD16-3
2 ea, 16 Amp 100 to 240 VAC 10 Amps 16 Amps 32 Amps
MPC-20VS32-3
1 ea, 32 Amp 100 to 240 VAC 10 Amps 32 Amps 32 Amps
MPC-20VD32-3
2 ea, 32 Amp 100 to 240 VAC 10 Amps 32 Amps 64 Amps
* In accordance with UL requirements for branch circuits, this value has been
de-rated to 80%.