Xerox 721P85600 Printer User Manual


 
PREINSTALLATION
3-18 XEROX DOCUPRINT 96/DOCUPRINT 96MX LPS INSTALLATION PLANNING GUIDE
DocuPrint 96/DocuPrint 96MX LPS power receptacle requirements
All power outlets must be dedicated only to this equipment. Ensure
that each power cord has a separate circuit.
You must use a power cord assembly (ELCI, RCD Inline, 220 VAC)
when using a source other than the system controller to provide
power to your keyboard/display. Contact your sales and service
representative to ensure the proper assembly is ordered and
installed.
Ensure that the power cord configurations match your receptacle
requirements (tables 3-7 and 3-8).
50 Hz systems: Consult with your local service representative to
determine the type of plug and receptacle to use with your 50 Hz
printer and system controller.
Table 3-7. Printer power receptacle requirements
Electrical environment Voltage/current Receptacle
U.S. and Canada 60 Hz 120/240/50A or
120/208/50A
NEMA 14-50R
International 50 Hz WYE 380, 400, 415/20A (WYE), 3
Phase, 5 wire
Per local code
International 50 Hz DELTA 220, 230, 240/30A (DELTA),
3 Phase, 4 wire
Per local code
Table 3-8. System controller and peripheral cabinet power
receptacle requirements
Electrical environment Voltage Current Receptacle
U.S. and Canada 60 Hz 208/240, 1 Phase or
220/230 (L1-L2)
15A NEMA 6-15R or
ANSI C73,
20R
International 50 Hz 220/230, 1 Phase 15A Per local code