PREINSTALLATION
XEROX DOCUPRINT 96/DOCUPRINT 96MX LPS INSTALLATION PLANNING GUIDE 3-19
50 Hz WYE printer outlet voltages
Note: 50 Hz WYE configurations only: Measure the WYE
connection voltages at the power source. Table 3-9 shows 415
voltages. Table 3-10 shows 380 and 400 voltages.
All power outlets must be dedicated only to this equipment. Ensure
that each power cord has a separate circuit.
Table 3-9. Printer (50 Hz only) WYE connection for 415 V
Service outlet
Service outlet
configuration Measurement Nominal Range
5 Wire 415 V Line 1 to Line 2 415 V RMS 374-457 V RMS
5 Wire 415 V Line 2 to Line 3 415 V RMS 374-457 V RMS
5 Wire 415 V Line 1 to Line 3 415 V RMS 374-457 V RMS
5 Wire 415 V Line 1 to Neutral 240 V RMS 216-264 V RMS
5 Wire 415 V Line 2 to Neutral 240 V RMS 216-264 V RMS
5 Wire 415 V Line 3 to Neutral 240 V RMS 216-264 V RMS
Table 3-10. Printer (50 Hz only) WYE connection for 380 V and
400 V Service outlet
Service outlet
configuration Measurement Nominal Range
5 Wire 380 V Line 1 to Line 2 380 V RMS 342-419 V RMS
5 Wire 380 V Line 2 to Line 3 380 V RMS 342-419 V RMS
5 Wire 380 V Line 1 to Line 3 380 V RMS 342-419 V RMS
5 Wire 380 V Line 1 to Neutral 220 V RMS 198-242 V RMS
5 Wire 380 V Line 2 to Neutral 220 V RMS 198-242 V RMS
5 Wire 380 V Line 3 to Neutral 220 V RMS 198-242 V RMS
5 Wire 400 V Line 1 to line 2 400 V RMS 358-438 V RMS
5 Wire 400 V Line 2 to line 3 400 V RMS 358-438 V RMS
5 Wire 400 V Line 1 to Line 3 400 V RMS 358-438 V RMS
5 Wire 400 V Line 1 to Neutral 230 V RMS 207-253 V RMS
5 Wire 400 V Line 2 to Neutral 230 V RMS 207-253 V RMS
5 Wire 400 V Line 3 to Neutral 230 V RMS 207-253 V RMS