PREINSTALLATION
3-20 XEROX DOCUPRINT 96/DOCUPRINT 96MX LPS INSTALLATION PLANNING GUIDE
50 Hz DELTA printer outlet voltages
Note: All power outlets must be dedicated only to this equipment.
Ensure that each power cord has a separate circuit.
50 Hz DELTA configurations only: Measure the DELTA connection
voltages at the power source. The required voltages are shown in
table 3-11.
Consult with your service representative to determine the type of plug
and receptacle to be used for your 50 Hz printer.
Table 3-11. Printer (50 Hz only) DELTA connection for 220/230/
240 V Service outlet
Service outlet
configuration Measurement Nominal Range
4 Wire 220 V Line 1 to Line 2 220 V RMS 198-242 V RMS
4 Wire 220 V Line 2 to Line 3 220 V RMS 198-242 V RMS
4 Wire 220 V Line 1 to Line 3 220 V RMS 198-242 V RMS
4 Wire 230 V Line 1 to line 2 230 V RMS 207-253 V RMS
4 Wire 230 V Line 2 to line 3 230 V RMS 207-253 V RMS
4 Wire 230 V Line 1 to line 3 230 V RMS 207-253 V RMS
4 Wire 240 V Line 1 to Line 2 240 V RMS 216-264 V RMS
4 Wire 240 V Line 2 to Line 3 240 V RMS 216-264 V RMS
4 Wire 240 V Line 1 to Line 3 240 V RMS 216-264 V RMS