MX28B1200/2400 MX28B1200/4800 –48 VDC User’s Manual Page 41
PARAMETER NAME/
[MENU LOCATION]
DESCRIPTION DISPLAY SCREENS /
DEFAULT SETTINGS
LVD 1 or 2 Option
Security Level {1}
[MODULES/LVD/SET-ALM]
Must be set to “Enable” if the unit has an LVD. If
the unit has an LVD, but it is disabled, the
controller will not disconnect the LVD.
LVD Option m+
Enable
LVD 1 or 2 Reset
Security Level {1}
[MODULES/LVD/PARAM]
LVD Reset (reconnect) threshold voltage.
LVD Reset m+
-48.00 V
LVD 1 or 2 Trip
Security Level {1}
[MODULES/LVD/PARAM]
LVD Trip (disconnect) threshold voltage.
LVD Trip m+
-42.00 V
LVD Alarm
Security Level {1}
[MODULES/LVD/SET-ALM]
The output relay that is energized when the
controller opens the LVD. If unit has a battery
LVD, no power will be available to turn on any
Output Relays.
LVD Open Alm m+
Minor
Model Programming
Security Level {2}
[SYSTEM/SETUP]
Model type number for the MX28B DC power
plant. Choose the MX28B-1200 if you have the
2500 Amp battery shunt. Choose the MX28B-
4800 if you have the 5000 Amp battery shunt.
NOTE: Changing the model number causes the
system to reinitialize.
Model m+
MX28B-1200
OEM R Gain
Security Level {2}
[OEM]
Voltage gain adjustment for factory calibration of
system voltage readings/settings.
OEM R Gain m+
1.000 V
OEM R Offset
Security Level {2}
[OEM]
Voltage offset adjustment for factory calibration of
system voltage readings/settings.
OEM R Offset m+
0.000 V
OEM S Gain
Security Level {2}
[OEM]
Current gain adjustment for factory calibration of
battery current readings/settings.
OEM S Gain m+
1.000 A
OEM S Offset
Security Level {2}
[OEM]
Current offset adjustment for factory calibration of
battery current readings/settings.
OEM S Offset m+
0.0 A
Output Relay 1 Alarm
Security Level {1}
[SYSTEM/OUT-RLY/RLY-
MAP]
Output Relay 6 Alarm
Security Level {1}
[SYSTEM/OUT-RLY/RLY-
MAP]
Output Relay 1 Alarm can be “mapped” to activate
other output relays (“Ignore” activates no
additional relays).
Output Relay 6 Alarm can be “mapped” to activate
other output relays (“Ignore” activates no
additional relays).
Out-Rly 1 Alm m+
Ignore
Out-Rly 6 Alm m+
Ignore
Output Relay 1 Alias
Security Level {1}
[SYSTEM/OUT-RLY/ALIAS]
Output Relay 6 Alias {1}
[SYSTEM/OUT-RLY/ALIAS]
An alternate name (alias) can be assigned to
Output Relay 1 if desired.
An alternate name (alias) can be assigned to
Output Relay 6 if desired.
Out-Rly 1 m+
Relay 1
Out-Rly 6 m+
Relay 6