MX28B1200/2400 MX28B1200/4800 –48 VDC User’s Manual Page 42
PARAMETER NAME/
[MENU LOCATION]
DESCRIPTION DISPLAY SCREENS /
DEFAULT SETTINGS
Output Relay 1 Delay
Security Level {1}
[SYSTEM/OUT-RLY/RLY-
MAP]
•
•
•
Output Relay 6 Delay
Security Level {1}
[SYSTEM/OUT-RLY/RLY-
MAP]
Delay between sensing of the alarm condition and
activation of Output Relay 1. An alarm condition
must exist for longer than the delay to be
activated.
•
•
•
Delay between sensing of the alarm condition and
activation of Output Relay 6. An alarm condition
must exist for longer than the delay to be
activated.
Out-Rly 1 Dly m+
0 sec
•
•
•
Out-Rly 6 Dly m+
0 sec
Output Relay Major Alias
Security Level {1}
[SYSTEM/OUT-RLY/ALIAS]
An alternate name (alias) can be assigned to the
major Relay if desired.
Relay Major m+
Major
Output Relay Minor Alias
Security Level {1}
[SYSTEM/OUT-RLY/ALIAS]
An alternate name (alias) can be assigned to the
Minor Relay if desired.
Relay Minor m+
Minor
PIN 1 change
Security Level {2}
[SYSTEM/SETUP]
Permanently change password (PIN) that permits
security Level 1 parameter changes - limited
access.
PIN m+
1111
PIN 2 Change
Security Level {2}
[SYSTEM/SETUP]
Permanently change password (PIN) that permits
security Level 2 parameter changes - unlimited
access.
PIN 2 m+
2222
PIN Entry
Security Level {0}
[PIN]
Screen for entry of the active password (PIN).
Before any changes can be made, the correct pin
for the desires security level must be entered.
Level 0 – full read access. Level 1 –full read and
limited write access. Level 2 – full read and write
access.
PIN m+
0000
Rectifier Communications Fail
Timeout
Security Level {1}
[MODULES/RECT/PARAM]
The maximum rectifier communications response
time allowed before a communications failure is
declared.
RectFailComm m+
1 min
Rectifier Configuration Alarm
Security Level {1}
[SYSTEM/SET-ALM]
The output relay energized if the rectifier
configuration differs from its stored configuration.
This occurs if a rectifier is added after
configuration.
Rect Cfg Alm m+
Minor
Rectifier Current Limit Alarm
Security Level {1}
[MODULES/RECT/SET-ALM]
The output relay that is energized or special
rectifier alarm group n of N that occurs when a
rectifier has been forced into the current limited
mode.
Rect CL Alm m+
n of N
Rectifier Current Limit Alarm
Status
{Status Only}
[MODULES/RECT/INFO]
The status will be “ON” if the rectifier has been
forced into its current limited mode. NOTE
: This
information can be viewed for each rectifier
installed by using the horizontal arrow keys.
Rect 1 CL #
OFF
Rectifier Current Output Status
{Status Only}
[MODULES/RECT/INFO]
A display of the DC output current for the
individual rectifier. NOTE
: This information can
be viewed for each rectifier installed by using
the horizontal arrow keys.
Rect 1 Curr #
24.9 A