American Power Conversion MX28B4800 Power Supply User Manual


 
MX28B1200/2400 MX28B1200/4800 –48 VDC User’s Manual Page 59
9. Ensure that all protective covers are replaced and that the battery is electrically non-
hazardous to personnel that could be working in the vicinity. Detail any discrepancies.
10. Download the Cellcorder to a PC and create a data file for each battery string. Keep a
copy of the results on disk.
7.4. Final Inspection:
6. Verify that the interior and exterior of the system is clean and free from debris.
7. Ensure all wires connected and bolts are properly tightened.
8. Ensure the following the User, Service, and Calibration parameters are set properly on
the controller (default settings are in parenthesis):
LVD (Param)
LVD1 Trip (-42.00 V)
LVD1 Reset (-48.00 V)
LVD2 Trip (-42.00 V)
LVD2 Reset (-48.00 V)
Batt (Set-alm)
Batt Disc Thr (10 A)
Batt (Param)
Batt Float (-54.00 V)
Batt Max Rech (50 A)
Batt (Comp)
Comp Method (OFF)
9. Verify on the status menu that the system is functioning correctly with no alarms.
10. Be sure to leave the site as orderly and neat as possible.