Chapter 5: CCM Appliance Commands 85
SPC Command
The SPC command changes settings for an SPC power control device.
NOTE: To access the control screen or command line interface provided by the SPC device, this command
should not be used, and the CCM appliance port to which the SPC device is attached should be configured as
TD=Console. When TD=SPC is configured, you cannot connect to the SPC device; all SPC device operations
are performed from the CCM appliance CLI.
Access right: SCON or PCON
Access level: ADMIN or APPLIANCEADMIN
Syntax
SPC <port>|ALL [MINLOAD=<amps>] [MAXLOAD=<amps>]
The following command sets a maximum load of 20 amps for the SPC device attached to the port
named spc3 on the CCM appliance.
spc spc3 max=20
SPC Socket Command
The SPC Socket command changes the settings or state for one or more sockets on an SPC power
control device.
NOTE: For standalone use of the SPC device, this command should not be used, and the CCM appliance port to
which the SPC device is attached should be configured as TD=Console.
Access right: SCON or PCON
Access level: ADMIN or APPLIANCEADMIN
Syntax
SPC <port>|ALL [SOCKET <socket>] [WAKE=ON|OFF] [ONMIN=<time>]
[OFFMIN=<time>] [POWER=ON|OFF|REBOOT]
Table 5.39: SPC Command Parameters
Parameter Description
<port>|ALL
Port number, port name or All, which indicates that the settings that follow should be
applied to all ports configured as TD=SPC. If the name contains spaces, it must be
enclosed in double quotes.
MINLOAD=<amps>
Minimum load in amperes in the range 0-30. A zero value indicates no minimum load.
Default = 0
MAXLOAD=<amps>
Maximum load in amperes in the range 0-30. A zero value indicates no maximum load.
Default = 0