A.2 CONNECT TO THE CARD - TERMINAL EMULATION, TELNET OR WEB INTERFACE
Upgrading the firmware requires connecting to the card with one of these interfaces.
A.2.1 Open the Terminal Emulation Interface - Serial Connection
To connect to the card using terminal emulation software with a
serial connection to the Web card:
1. Open a terminal emulation application, such as
HyperTerminal.
To do this:
•Click the Start button, then Programs, Accessories,
Communications and finally HyperTerminal.
2. In the Connection Description window, enter a name for the
connection—for example, GXT2U—then click OK.
3. In the Connect To window:
Choose COM3 from the Connect Using drop-down list.
•Click OK.
4. In the COM3 Properties window, enter the communication
settings shown in Table A3.
5. When the message at right appears in the HyperTerminal
window, press the Enter key.
A.2.2 Open the Terminal Emulation Interface - TCP/IP Connection
To connect to the card using terminal emulation software with
an Ethernet connection to the Web card:
1. Open a terminal emulation application, such as
HyperTerminal.
To do this:
•Click the Start button, then Programs, Accessories,
Communications and finally HyperTerminal.
2. In the Connection Description window, enter a name for the
connection—for example, GXT2U—then click OK.
3. In the Connect To window:
Choose TCP/IP (Winsock) from the Connect Using
drop-down list.
Enter the IP address of the Web card—for example,
192.168.0.125—in the Host Address box, then click OK.
4. When the message at right appears in the HyperTerminal window,
press the Enter key.
5. Enter the Administrator username and password (both are case-
sensitive):
a. Login (username—default is Liebert)
b. Password (default is Liebert)
Name
COM3
Connection
settings
Table A3 Communication settings
Baud Rate: 9600
Data Bits: 8
Parity: None
Stop Bits: 1
Flow Control: None
Name
TCP/IP
(Winsock)
RTCS v2.96.00 Telnet server
Service Port Manager Active