REV. 5 7/6/2007
Liebert Monitoring Group –Development
7
Liebert Nx
Supported Modbus Points
Data Point Status Coil # of Reg. Scale Notes / Units
Economode 10005 5
DC-To-DC Converter
On
10042
Battery Charge
Compensation
10046
Inverter Ready 10047
Power Factor
Correction State 10050
Battery Charge Mode 10051
Load On Inverter 10073
Bypass Active 10074
Battery Under Test 10082
Load On Battery 10128
Overload Transfer To
Bypass 10131
Input Switch Open 10137
Generator
Disconnected 10141
Bypass Transfer
Count Block 10147
Static Bypass Switch
Disabled 10148
Low Battery -
Shutdown Imminent
10152
Output Overload 10154
UPS Load Joint
Mode 10156
Output Off 10158
Inverter
Unsynchronized 10160
Main Neutral Lost 10161
Fan Failure 10169
Ambient Over
Temperature 10173
Rectifier Over
Temperature 10174
Rectifier Inductor
Over Temperature 10175
Inverter Over
Temperature 10176
Inverter Inductor
Over Temperature
10177
Battery Converter 10179