REV. 5 7/6/2007
Liebert Monitoring Group –Development
15
Liebert PowerSure Interactive 2
Supported Modbus Points
Data Point
Status Coil # of Reg. Scale Notes / Units
Audible Alarm Enabled
10002 2 1 1
Automatic Battery Test
Enabled 10003 3 1 1
DC-To-DC Converter
On
10042 1 1
Battery Charger On
10044 1 1
Load Circuit 1 State
10057 1 1
Load Circuit 2 State
10058 1 1
Load Circuit 3 State
10059 1 1
Load Circuit 4 State
10060 1 1
Load Circuit 5 State
10061 1 1
Load Circuit 6 State
10062 1 1
Load Circuit 7 State
10063 1 1
Load Circuit 9 State
10065 1 1
Load Circuit 10 State
10066 1 1
Load Circuit 11 State
10067 1 1
Load Circuit 12 State
10068 1 1
Load Circuit 13 State
10069 1 1
Load Circuit 14 State
10070 1 1
Load Circuit 15 State
10071 1 1
Load Circuit 16 State
10072 1 1
Load On Inverter
10073 1 1
Boost Mode On
10075 1 1
Buck Mode On
10076 1 1
Replace Battery
10081 1 1
Battery Under Test
10082 1 1
Shutdown Reason -
Over Temperature
10086 1 1
Shutdown Reason -
Overload 10087 1 1
Shutdown Reason -
Output Short
10089 1 1
Shutdown Reason -
Line Neutral Swap
10090 1 1
Shutdown Reason -
Low Battery 10092 1 1
Shutdown Reason -
Remote Shutdown
10093 1 1
Shutdown Reason -
Input Under Voltage
10094 1 1
Shutdown Reason -
10096 1 1