Emerson OpenComms-485 Network Card User Manual


 
REV. 5 7/6/2007
Liebert Monitoring Group –Development
28
Input Voltage L1 30153 1 1 V
Input Current 30154 1 1 A
Bypass Voltage L1 30159 1 1 V
Bypass Current L1 30160 1 1 A
Output Voltage L1 30163 1 1 V
Output Current L1 30164 1 1 A
Input Voltage L2 30203 1 1 V
Input Current L2 30204 1 1 A
Bypass Voltage L2 30209 1 1 V
Bypass Current L2 30210 1 1 A
Output Voltage L2 30213 1 1 V
Output Current L2 30214 1 1 A
Input Voltage L3 30253 1 1 V
Input Current L3 30254 1 1 A
Bypass Voltage L3 30259 1 1 V
Bypass Current L3 30260 1 1 A
Output Voltage L3 30263 1 1 V
Output Current L3 30264 1 1 A
Black Out Count 30301 1 1
Brown Out Count 30302 1 1
Transient Count 30301 1 1
Silent Audible Alarm 40101 any value
Battery Start 40102 1 1 1=Start, 0=Abort
Open UPS Output
Switch
40104 Delay time in Second, last digit
will be ignored
Reboot UPS Output
Switch
40105 1 1 Delay time in Second, last digit
will be ignored
Close UPS Output
Switch
40106 Delay time in Second, last digit
will be ignored
Transfer Load to
Bypass
40107 1 1 any value
Transfer Load to
Inverter
40108 any value
Reset UPS Statistic
data
40111 1 1 any value
Turn UPS Outlets On 40112 1 1 Bitmap mask for Outlet 1-16. all
bits set to 1 will be turn On
Turn UPS Outlets Off 40113 1 1 Bitmap mask for Outlet 1-16. all
bits set to 1 will be turn Off