REV. 5 7/6/2007
Liebert Monitoring Group –Development
27
Battery Charger Fail 10234 1 1
Data Point
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Number Of Input Lines 30004 40004 1 1 Bits 12 - 15
Number Of Bypass
Lines
30004 40004 1 1 Bits 4 - 7
Number Of Output
Lines
30004 40004 1 1 Bits 8 - 11
Number Of
SubModules
30009 40009 1 1
Load Circuit Present 30013 40013 1 There are 16 possible Load
Circuits. So each bit represents 1
load circuit. Load Circuit 1 is bit
0, Load Circuit 2 is bit 1 and so
on. If the bit is 1 then the Load
Circuit is supported.
Nominal Power Rating 30021 40021 2 1 VA
Nominal Input Voltage 30027 40027 1 1 V
Nominal Output
Voltage
30028 40028 1 1 V
Nominal Static Bypass
Switch Voltage
30029 40029 1 1 V
Nominal Input Current 30030 40030 1 1 A
Nominal Input
Frequency
30031 40031 1 10 Hz
Nominal Output
Frequency
30032 40032 1 10 Hz
Nominal Power Factor 30033 40033 1 100
Nominal Battery
Voltage
30034 40034 1 1 V
Device Low Battery
Time
30053 40053 1 1 min
Load (Apparent
Power)
30102 2 1 VA
Load (Real Power) 30104 2 1 W
Load / Capacity 30106 1 1 %
Input Frequency 30107 1 10 Hz
Output Frequency 30108 1 10 Hz
Bypass Frequency 30109 1 10 Hz
Battery Charge Status 30112 1 1 1 - 100% Charged
2 - Less than 100% Charged
Battery Voltage 30113 1 1 V
Battery Current 30114 1 1 A
Battery Time
Remaining
30115 1 1 min
Battery Charge
Percentage
30116 1 1 %
Battery Test Result 30130 1 1 1 - Unknown
2 - Passed
3 - Failed
4 - In Progress
5 - System Failure
6 - Inhibited