Emerson OpenComms-485 Network Card User Manual


 
REV. 5 7/6/2007
Liebert Monitoring Group –Development
21
Battery Charge
Status
30112 1
1 - 100% Charged
2 - Less than 100% Charged
3 - Charging
4 - Discharging
5 - Float Charging
6 - Equalize Charging
Battery Voltage
30113 1 1
V
Battery Time
Remaining 30115 1 1
min
Battery Charge
Percentage
30116 1 1
%
Ambient
Temperature 30119 1 1
deg C
Battery Test
Result
30130 1
1 - Unknown
2 - Passed
3 - Failed
4 - In Progress
5 - System Failure
6 - Inhibited
Input Voltage L1
30153 1 1
V
Bypass Voltage L1
30159 1 1
V
Output Voltage L1
30163 1 1
V
Output Current L1
30164 1 1
A
Input Maximum
Voltage L1
30180 1 1
V
Input Minimum
Voltage L1 30181 1 1
V
Output Maximum
Voltage L1 30182 1 1
V
Output Minimum
Voltage L1
30183 1 1
V
Black Out Count
30301 1 1
Brown Out Count
30302 1 1