Emerson OpenComms-485 Network Card User Manual


 
REV. 5 7/6/2007
Liebert Monitoring Group –Development
16
Hardware
Load On Battery
10128 1 1
Output Off Pending
10151 1 1
Low Battery - Shutdown
Imminent
10152 1 1
Output Overload
10154 1 1
Over Temperature
Warning 10171 1 1
Input Power Supply Fail
10186 1 1
Input Over Voltage
10187 1 1
Input Under Voltage
10188 1 1
Input BrownOut
10189 1 1
Bad Input Frequency
10190 1 1
Output Under Voltage
10218 1 1
Output Over Voltage
10219 1 1
Charger Failed
10234 1 1
Battery Under Voltage
10241 1 1
Battery Over Voltage
10242 1 1
Data Point
Input Register Holding Register # of Reg. Scale Notes / Units
Number Of Input Lines
30004 40004 1 1 Bits 12 - 15
Number Of Output
Lines 30004 40004 1 1 Bits 8 - 11
Number Of SubModules
30009 40009 1 1
Load Circuit Present
30013 40013 1
There are 16 possible
Load Circuits. So each
bit represents 1 load
circuit. Load Circuit 1 is
bit 0, Load Circuit 2 is bit
1 and so on. If the bit is
1 then the Load Circuit
is supported.
Nominal Power Rating
30021 40021 2 1 VA
Nominal Input Voltage
30027 40027 1 1 V
Nominal Output Voltage
30028 40028 1 1 V
Nominal Input Current
30030 40030 1 1 A
Nominal Input
Frequency 30031 40031 1 10 Hz
Nominal Output
Frequency 30032 40032 1 10 Hz
Nominal Power Factor
30033 40033 1 100
Nominal Battery Voltage
30034 40034 1 1 V
Nominal Battery
Capacity 30037 40037 1 1 minutes
Nominal Battery Float
Voltage 30038 40038 1 1 V
Auto Restart Delay
30051 40051 1 1 seconds
Device Low Battery
Time
30053 40053 1 1 min