REV. 5 7/6/2007
Liebert Monitoring Group –Development
35
Free cooling run
hours
30146 - 1 Hour S505
Electrical Heaters
#1 run hours
30147 - 1 Hour S507
Electrical Heaters
#2 run hours
30148 - 1 Hour S508
Electrical Heaters
#3 run hours
30149 - 1 Hour S509
Hot Water / Hot
Gas run hours
30150 - 1 Hour S506
Daily High
Temperature
30151 - x10 C° S313
Daily High Temp
Time
30152 - x1 Hh:mm S313
Daily Low
Temperature
30153 - x10 C° S314
Daily Low Temp
Time
30154 - x1 Hh:mm S314
Daily High
Humidity
30155 - x1 %RH S315
Daily High Hum
Time
30156 - x1 Hh:mm S315
Daily Low
Humidity
30157 - x1 %RH S316
Daily Low Hum
Time
30158 - x1 Hh:mm S316
[1] Any non-recognized alarm code by current firmware received from the DS control will trigger this event.
[2] Timer mode: 0 = no, 1= yes.
[3] Type of DT Room-Glycol: 0 = no, 1=contact, 2=value.
[4] Predictive Hum Control: 0=relative, 1=compensated, 2=predictive.
[5] Temp Control Algorithm: 0=proportional, 1=PD, 2=PDI; 3=intelligent;
[6] When VFD is set to manual mode(coil 22), the host can control the VFD by the value of register 40019. The Manual
VSD Timer will start to count down. Once it reaches 0, the VFD control mode will switch to auto. The host will need to
periodically reset this timer in order to maintain the manual mode. Consult factory for BMS timer information.
[7] Operating State
: Bit 0-1: 00 unit off, 01 unit on, 10 unit standby
Bit 2-3: 00 auto, 01 manual
Bit 4-7: 0000 none,
0001 local user,
0010 alarm,
0011 schedule,
0100 remote user,
0101 external device,
0110 local display
[8] Alarm state bit map: Bit0 =. Reset state
bit1 = Active state ;
bit2 = Acknowledge state,
bit3-7 = Alarm Type,: 00000: Message
00001: Warning
00010: Alarm
[9] Free-cool state: 0= Off, 1= Start, 2= On.