Emerson OpenComms-485 Network Card User Manual


 
REV. 5 7/6/2007
Liebert Monitoring Group –Development
24
Input Phase Rotation
Error
10191 1 1
Bypass Phase Missing 10201 1 1
Bypass Input Voltage
Fail
10202 1 1
Bypass Under Voltage
Fail
10203 1 1
Bypass Under Voltage
Warning
10204 1 1
Bypass Over Voltage
Fail
10205 1 1
Bypass Over Voltage
Warning
10206 1 1
Output Under Voltage 10218 1 1
Output Over Voltage 10219 1 1
Output Short Circuit 10220 1 1
Module with Active
Alarm
10304 1 1
Data Point
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Number Of Input Lines 30004 40004 1 1 Bits 12 - 15
Number Of Bypass
Lines
30004 40004 1 1 Bits 4 - 7
Number Of Output
Lines
30004 40004 1 1 Bits 8 - 11
Number Of Sub-
Modules
30009 40009 1 1
Nominal Power Rating 30021 40021 2 1 VA
Nominal Input Voltage 30027 40027 1 1 V
Nominal Output
Voltage
30028 40028 1 1 V
Nominal Static Bypass
Switch Voltage
30029 40029 1 1 V
Nominal Input Current 30030 40030 1 1 A
Nominal Output
Frequency
30032 40032 1 10 Hz
Nominal Power Factor 30033 40033 1 100
Nominal Battery
Voltage
30034 40034 1 1 V
Load (Apparent
Power)
30102 2 1 VA
Load (Real Power) 30104 2 1 W
Load / Capacity 30106 1 1 %
Output Frequency 30108 1 10 Hz
Bypass Frequency 30109 1 10 Hz
Battery Charge Status 30112 1 1 - 100% Charged
2 - Less than 100% Charged
Battery Voltage 30113 1 1 V
Battery Current 30114 1 1 A
Battery Time
Remaining
30115 1 1 min
Battery Charge
Percentage
30116 1 1 %