Emerson OpenComms-485 Network Card User Manual


 
REV. 5 7/6/2007
Liebert Monitoring Group –Development
4
Liebert Nfinity
Supported Modbus Points
Data Point
Status Coil
# of
Reg.
Scale Notes/ Units
Automatic Battery Test
Enabled
10003 3 1 1
Battery Charger On 10044 1 1
Inverter Ready 10047 1 1
Power Factor Correction
State 10050 1 1
Load On Inverter 10073 1 1
Bypass Active 10074 1 1
Replace Battery 10081 1 1
Battery Under Test 10082 1 1
Load On Battery 10128 1 1
Load On Bypass 10129 1 1
Load On Manual Bypass 10132 1 1
Load Transferred To
Bypass Due To UPS Fault
10134 1 1
Transfer Inhibit 10146 1 1
Output Off Pending 10151 1 1
Low Battery - Shutdown
Imminent 10152 1 1
Output Overload 10154 1 1
UPS Overload 10155 1 1
Output Off 10158 1 1
Check Air Filter - Replace 10170 1 1
Transformer Over
Temperature
10178 1 1
Input Power Supply Fail 10186 1 1
Internal Device
Communication Failure 10284 1 1
Device Active Alarm 10290 1 1
Main Control Warning 10291 1 1
Redundant Control Warning 10292 1 1
Control Module Failure 10293 1 1
Redundant Control Module
Failed 10294 1 1
User Interface Module
Failed 10295 1 1