REV. 5 7/6/2007
Liebert Monitoring Group –Development
12
Liebert PowerSure Interactive
Supported Modbus Points
Data Point Status Coil # of Reg. Scale Notes /Units
Audible Alarm Enabled 10002 2 1 1
Automatic Battery Test
Enabled
10003 3 1 1
Battery Charge
Compensation 10046 1 1
Inverter Ready 10047 1 1
Load Circuit 1 State 10057 1 1
Load Circuit 2 State 10058 1 1
Load Circuit 3 State 10059 1 1
Load Circuit 4 State 10060 1 1
Load Circuit 5 State 10061 1 1
Load Circuit 6 State 10062 1 1
Load Circuit 7 State 10063 1 1
Load Circuit 8 State 10064 1 1
Load Circuit 9 State 10065 1 1
Load Circuit 10 State 10066 1 1
Load Circuit 11 State 10067 1 1
Load Circuit 12 State 10068 1 1
Load Circuit 13 State 10069 1 1
Load Circuit 14 State 10070 1 1
Load Circuit 15 State 10071 1 1
Load Circuit 16 State 10072 1 1
Load On Inverter 10073 1 1
Boost Mode On 10075 1 1
Buck Mode On 10076 1 1
Battery Under Test 10082 1 1
Shutdown Reason - Over
Temperature 10086 1 1
Shutdown Reason -
Overload 10087 1 1
Shutdown - Output Short 10089 1 1
Shutdown Reason -
Remote Shutdown 10093 1 1
Load On Battery 10128 1 1
Output Off Pending 10151 1 1
Low Battery - Shutdown
Imminent
10152 1 1
Output Overload 10154 1 1
Over Temperature Warning 10171 1 1
Battery Over Temperature
CB Trip 10172 1 1