4.1.11. System Monitor Command – Timeclock Status
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name, Scan_Interval, Data_Array_Name, Data_Array_Offset, Function, Node_Name, GRAFIK_command, Area, Length
Tclk_sts_00, 1s, Tclk_status, 0, rdbc, LUT_GRF6_0, timeclock_status, 0, 4
Tclk_sts_01, 1s, Tclk_status, 4, rdbc, LUT_GRF6_0, timeclock_status, 1, 4
Data storage in Data Array
Position from offset Description
0 Schedule number
1 Next event type (1 = no more events, 2 = timeclock disabled, 3 = astronomic event, 4 = realtime event )
2 Next event time ( minutes past midnight )
3 Next script
Note: This command stores 4 data values. To prevent overlaps, remember to increment Data_Array_Offset by 4 when referencing the same Data
Array with other Map Descriptors.
4.1.12. System Monitor Command – Zone Intensity
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name, Scan_Interval, Data_Array_Name, Data_Array_Offset, Function, Node_Name, GRAFIK_command, Zone, Length
Zn_int_00, 1s, Zone_int, 0, rdbc, LUT_GRF6_0, zone_intensity, 0, 1
Zn_int_01, 1s, Zone_int, 1, rdbc, LUT_GRF6_0, zone_intensity, 1, 1
Data storage in Data Array
Position from offset Description
0 Zone intensity ( 0-127 )
Note: This command stores 1 data value. To prevent overlaps, remember to increment Data_Array_Offset by 1 when referencing the same Data
Array with other Map Descriptors.