4.1.31. System Control Commands containing no Parameters: Enable wallstation(s)
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, GRAFIK_command, DA_Lut_List, DA_Lut_List_Offset, Length
Enable_ws, Lut_triggers, 14, awt, LUT_GRF6_0, ena_wallstation, Ctrl_ws_list, 0, 1
DA_Lut_List data setup
Position from DA_Lut_List_Offset Description
0 Link number ( 0-11 ) of Station ID 0
1 Station on link ( 0-31 ) of Station ID 0
.. ..
62 Link number ( 0-11 ) of Station ID 31
63 Station on link ( 0-31 ) of Station ID 31
Note: 1 to 32 station ids may be used to enable wallstations. To trigger the command, write the number of station IDs into the Data Array specified
by Data_Array_Name at Data_Array_Offset
4.1.32. System Control Commands containing no Parameters: Disable wallstation(s)
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, GRAFIK_command, DA_Lut_List, DA_Lut_List_Offset, Length
Disable_ws, Lut_triggers, 15, awt, LUT_GRF6_0, dis_wallstation, Ctrl_ws_list, 0, 1
DA_Lut_List data setup
Position from DA_Lut_List_Offset Description
0 Link number ( 0-11 ) of Station ID 0
1 Station on link ( 0-31 ) of Station ID 0
.. ..
62 Link number ( 0-11 ) of Station ID 31
63 Station on link ( 0-31 ) of Station ID 31
Note: 1 to 32 station ids may be used to disable wallstations. To trigger the command, write the number of station IDs into the Data Array specified
by Data_Array_Name at Data_Array_Offset.