FieldServer FS-8700-84 Computer Drive User Manual


 
FS-8700-84_Lutron_eLumen Driver Manual Page 25 of 36
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com
4.1.33. System Control Commands containing no Parameters: Simulate wallstation(s) switch press
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, GRAFIK_command, DA_Lut_List, DA_Lut_List_Offset, Length
Ws_sw_press, Lut_triggers, 16, awt, LUT_GRF6_0, sim_ws_sw_press, Sim_sw_list, 0, 1
DA_Lut_List data setup
Position from DA_Lut_List_Offset Description
0 Link number ( 0-11 )
1 Station of link ( 0-31 ) of Switch ID 0
2 Switch on station ( 0-31 ) of Switch ID 0
3 Station of link ( 0-31 ) of Switch ID 1
4 Switch on station ( 0-31 ) of Switch ID 1
.. ..
63 Station of link ( 0-31 ) of Switch ID 31
64 Switch on station ( 0-31 ) of Switch ID 31
Note: 1 to 32 switch ids may be used in a single command. To trigger the command, write the number of switch IDs into the Data Array specified
by Data_Array_Name at Data_Array_Offset.