FieldServer FS-8700-84 Computer Drive User Manual


 
FS-8700-84_Lutron_eLumen Driver Manual Page 20 of 36
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com
4.1.25. System Control Commands containing no Parameters: Run script(s)
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, GRAFIK_command, DA_Lut_List, DA_Lut_List_Offset, Length
Run_script, Lut_triggers, 8, awt, LUT_GRF6_0, run_script, Script_list, 0, 1
DA_Lut_List data setup
Position from DA_Lut_List_Offset Description
0-63 Numbers of scripts to run
4.1.26. System Control Commands containing no Parameters: Toggle system variable value
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, GRAFIK_command, DA_Lut_List, DA_Lut_List_Offset, Length
Toggle_sys_var, Lut_triggers, 9, awt, LUT_GRF6_0, toggle_sys_var_val, Var_list, 0, 1
DA_Lut_List data setup
Position from DA_Lut_List_Offset Description
0-31 Numbers of system variables to toggle