FieldServer FS-8700-84 Computer Drive User Manual


 
FS-8700-84_Lutron_eLumen Driver Manual Page 27 of 36
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com
4.1.36. System Control Commands Containing Parameters: Toggle zone
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, GRAFIK_command, DA_Lut_List, DA_Lut_List_Offset, DA_Lut_Parms, DA_Lut_Parms_Offset, Length
Toggle_zone, Lut_triggers, 19, awt, LUT_GRF6_0, toggle_zone, Zone_list, 0, Zone_pars, 0, 1
DA_Lut_List setup
Position from DA_Lut_List_Offset Description
0-63 Zone(s) to toggle
DA_Lut_Parms setup
Position from DA_Lut_Parms_Offset Description
0 Fade cycles
4.1.37. System Control Commands Containing Parameters: Fade zone(s) to level
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, GRAFIK_command, DA_Lut_List, DA_Lut_List_Offset, DA_Lut_Parms, DA_Lut_Parms_Offset, Length
Fade_to_level, Lut_triggers, 20, awt, LUT_GRF6_0, fade_zone, Zone_list, 0, Zone_pars, 0, 1
DA_Lut_List setup
Position from DA_Lut_List_Offset Description
0-63 Zone(s) to fade to level
DA_Lut_Parms setup
Position from DA_Lut_Parms_Offset Description
0 Level to fade to ( 0-127 )
1 Fade cycles
2 Delay cycles