4.1.34. System Control Commands containing no Parameters: Simulate wallstation(s) switch release
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, GRAFIK_command, DA_Lut_List, DA_Lut_List_Offset, Length
Ws_sw_rls, Lut_triggers, 17, awt, LUT_GRF6_0, sim_ws_sw_rls, Sim_sw_list, 0, 1
DA_Lut_List data setup
Position from DA_Lut_List_Offset Description
0 Link number ( 0-11 )
1 Station of link ( 0-31 ) of Switch ID 0
2 Switch on station ( 0-31 ) of Switch ID 0
3 Station of link ( 0-31 ) of Switch ID 1
4 Switch on station ( 0-31 ) of Switch ID 1
.. ..
63 Station of link ( 0-31 ) of Switch ID 31
64 Switch on station ( 0-31 ) of Switch ID 31
Note: 1 to 32 switch ids may be used in a single command. To trigger the command, write the number of switch IDs into the Data Array specified
by Data_Array_Name at Data_Array_Offset.
4.1.35. System Control Commands containing no Parameters: Stop scene ramp down
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, GRAFIK_command, DA_Lut_List, DA_Lut_List_Offset, Length
Stop_scn_rmp_dn, Lut_triggers, 18, awt, LUT_GRF6_0, stop_scene_ramp_dn, Area_list, 0, 1
DA_Lut_List data setup
Position from DA_Lut_List_Offset Description
0-31 Area(s) with scenes to stop ramp down
Note: After setting up the area numbers to stop scene ramps in the DA_Lut_List Data Array, trigger this command by writing the number of areas
into the Data Array specified by Data_Array_Name at an offset specified by Data_Array_Offset.