FieldServer FS-8700-84 Computer Drive User Manual


 
FS-8700-84_Lutron_eLumen Driver Manual Page 18 of 36
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com
4.1.19. System Control Commands containing no Parameters: – Select System Scene(s)
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, GRAFIK_command, DA_Lut_List, DA_Lut_List_Offset, Length
Sel_scene, Lut_triggers, 2, awt, LUT_GRF6_0, sel_scene, Scene_list, 0, 1
DA_Lut_List data setup
Position from DA_Lut_List_Offset Description
0-63 System scenes to select
4.1.20. System Control Commands containing no Parameters: – Disable Timeclock until Enabled
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, GRAFIK_command, DA_Lut_List, DA_Lut_List_Offset, Length
Dis_tck_u_e, Lut_triggers, 3, awt, LUT_GRF6_0, dis_tclk_u_e, Area_list, 0, 1
DA_Lut_List data setup
Position from DA_Lut_List_Offset Description
0-31 Area timeclocks to disable
4.1.21. System Control Commands containing no Parameters: – Disable timeclock until end of day or
enable issued
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, GRAFIK_command, DA_Lut_List, DA_Lut_List_Offset, Length
Dis_tck_u_eodoe, Lut_triggers, 4, awt, LUT_GRF6_0, dis_tclk_u_eodoe, Area_list, 0, 1
DA_Lut_List data setup
Position from DA_Lut_List_Offset Description
0-31 Area timeclocks to disable