FieldServer FS-8700-84 Computer Drive User Manual


 
FS-8700-84_Lutron_eLumen Driver Manual Page 30 of 36
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com
4.1.41. System Control Commands Containing Parameters: Flash zones aka “Multi level ( Flash or
Warn or Chase )“
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, GRAFIK_command, DA_Lut_List, DA_Lut_List_Offset, DA_Lut_Parms, DA_Lut_Parms_Offset, Length
Flash_zone, Lut_triggers, 24, awt, LUT_GRF6_0, flash_zone, Zone_list, 0, Zone_pars, 0, 1
DA_Lut_List setup
Position from DA_Lut_List_Offset Description
0-63 Zone(s) to flash
DA_Lut_Parms setup
Position from DA_Lut_Parms_Offset Description
0 Delay1 cycles
1 Intensity1 ( 0-127 )
2 Fade1 cycles
3 Delay2 cycles
4 Intensity2 ( 0-127 )
5 Fade2 cycles
6 Delay2 cycles
7 Repeat ( 0-255 )
4.1.42. System Control Commands Containing Parameters: Ramp scene zones up
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, GRAFIK_command, DA_Lut_List, DA_Lut_List_Offset, DA_Lut_Parms, DA_Lut_Parms_Offset, Length
Rmp_scn_zns_up, Lut_triggers, 25, awt, LUT_GRF6_0, ramp_scene_zones_up, Area_list, 0, Area_pars, 0, 1
DA_Lut_List setup
Position from DA_Lut_List_Offset Description
0-31 System area numbers
DA_Lut_Parms setup
Position from DA_Lut_Parms_Offset Description
0 Unaffected intensity ( 0-128 )
1 Initial rate step size
2 Repeat rate step size