FieldServer FS-8700-84 Computer Drive User Manual


 
FS-8700-84_Lutron_eLumen Driver Manual Page 31 of 36
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com
4.1.43. System Control Commands Containing Parameters: Ramp scene zones down
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, GRAFIK_command, DA_Lut_List, DA_Lut_List_Offset, DA_Lut_Parms, DA_Lut_Parms_Offset, Length
Rmp_scn_zns_dn, Lut_triggers, 26, awt, LUT_GRF6_0, ramp_scene_zones_dn, Area_list, 0, Area_pars, 0, 1
DA_Lut_List setup
Position from DA_Lut_List_Offset Description
0-31 System area numbers
DA_Lut_Parms setup
Position from DA_Lut_Parms_Offset Description
0 Unaffected intensity ( 0-128 )
1 Initial rate step size
2 Repeat rate step size
4.1.44. System Control Commands Containing Parameters: Select system scene(s) using override
times
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, GRAFIK_command, DA_Lut_List, DA_Lut_List_Offset, DA_Lut_Parms, DA_Lut_Parms_Offset, Length
Sel_scene_oride, Lut_triggers, 27, awt, LUT_GRF6_0, sel_scene_override, Scene_list, 0, Scene_pars, 0, 1
DA_Lut_List setup
Position from DA_Lut_List_Offset Description
0-63 System scene numbers
DA_Lut_Parms setup
Position from DA_Lut_Parms_Offset Description
0 Fade cycles
1 Delay cycles