FieldServer FS-8700-84 Computer Drive User Manual


 
FS-8700-84_Lutron_eLumen Driver Manual Page 28 of 36
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com
4.1.38. System Control Commands Containing Parameters: Ramp zone(s) up
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, GRAFIK_command, DA_Lut_List, DA_Lut_List_Offset, DA_Lut_Parms, DA_Lut_Parms_Offset, Length
Rmp_zones_up, Lut_triggers, 21, awt, LUT_GRF6_0, ramp_zones_up, Zone_list, 0, Zone_pars, 0, 1
DA_Lut_List setup
Position from DA_Lut_List_Offset Description
0-63 Zone(s) to ramp up
DA_Lut_Parms setup
Position from DA_Lut_Parms_Offset Description
0 Initial rate step size
1 Repeat rate step size
4.1.39. System Control Commands Containing Parameters: Ramp zone(s) down
// Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, GRAFIK_command, DA_Lut_List, DA_Lut_List_Offset, DA_Lut_Parms, DA_Lut_Parms_Offset, Length
Rmp_zones_up, Lut_triggers, 22, awt, LUT_GRF6_0, ramp_zones_down, Zone_list, 0, Zone_pars, 0, 1
DA_Lut_List setup
Position from DA_Lut_List_Offset Description
0-63 Zone(s) to ramp down
DA_Lut_Parms setup
Position from DA_Lut_Parms_Offset Description
0 Initial rate step size
1 Repeat rate step size