Chapter 1 Hardware Configurations
1.5 Power Distribution Units (Only for Regions Other than EMEA&I)
ETERNUS DX80 S2/DX90 S2 Disk storage system User’s Guide -Site Planning-
Copyright 2013 FUJITSU LIMITED P3AM-4822-12ENZ0
26
■ Power distribution unit for DX80 S2/DX90 S2 (AC200-240V, 2U, Max 8 enclosures
connection)
There are 16 outlets.
Figure 1.25 Power distribution unit (AC200-240V, 2U, Max 8 enclosures connection)
The following table shows the specifications of a power distribution unit and the AC cables that are provided.
Table 1.10 Power distribution unit (AC200-240V, 2U, Max 8 enclosures connection) and provided AC cable
specifications
Item Specifications
Power Voltage AC200 - 240V
Phase Single
Frequency 50Hz/60Hz
Input cable Connection type Straight-through ↔ NEMA L6-30P
Length 4m
Quantity 2
Output cable Connection type IEC60320-C13 ↔ IEC60320-C14
Length 3m
Quantity 16
Outlets (OUTPUT)