Fujitsu XG2600 Switch User Manual


 
XG2600 Hardware Guide Chapter 2 Installation
Requirements for Installation Environment
28
Installation Requirements
The product is specifically designed for rack-mounting.
Check-list
Check the following items.
2.1.2 Space Requirements
When installing the switch and providing maintenance, ensure the space below is maintained.
Ensuring the Space for Installation (Maintenance) of the Switch
Internal cooling fans of the switch allow the air intake and exhaust performed at both at the Interface Side and Fan Unit Side.
Ensure the indicated space below and do not put anything which avoids airflow.
Check Item Check Result
Nothing is put on the switch.
Vents are not obstructed.
The switch is not located on the table or not stuck on another switch.
The switch is not located under direct sunshine, near heating appliance, under high humidity
or in a dusty area..
The switch is not located on unstable places where vibrating, or tilting.
"For Safe Use of the Product" has been thoroughly read (pg.8)
Reference
Reference
rack
300mmormore
800mm
800mm
XG2600
90mm
ormore
150mm
ormore
Backspacefor
themaintenance
Spaceforthe
maintenance/
installation
Spaceforthe
maintenance/
installation
300mmormore
Frontspacefor
themaintenance
19"rackWidth
19"rack
Depth