GE Energy Services
BECCO2200 DCA
Configuration Guide
A164-0CG-1.00-2 Restricted
4
Full
☞
☞☞
☞NOTE: The actual number of Binary Output points required must be incremented
by the number of Mode Download Pseudo Controls configured.
2.1.1 Binary Inputs
When communication is established with a device and valid data is returned for the binary input
point, the point is turned on-line and communication OK. If communication between the device
and the point fails, all binary input points associated with the device will be set off-line and
communication failed.
2.1.2 Binary Outputs
On startup, all pseudo controls associated with a valid device and all Mode Download Pseudo
Controls are placed on-line and communication OK. When communication is established with a
device, the remaining binary outputs are set on-line and communication OK. If communication
between the device and the points fails, all binary output points, excluding pseudo controls, will
be set off-line and communication failed.
2.1.3 Counters
When communication is established with a device and valid data is returned for the counter, the
point is turned on-line and communication OK. If communication between the device and the
point fails, all counters associated with the device will be set off-line and communication failed.
2.1.4 Analog Inputs
When communication is established with a device and valid data is returned for the analog input
point, the point is turned on-line and communication OK. If communication between the device
and the point fails, all analog input points associated with the device will be set off-line and
communication failed.
2.1.5 Analog Outputs
On startup, all analog outputs associated with a valid device are placed on-line and
communication OK. If communication between the device and the point fails, all analog output
points associated with the device will be set off-line and communication failed.
2.1.6 Device Status
When communication is established with a device, the device status point is set on-line and
communication OK. If communication between the device and the point fails, the device status
point will be set off-line and communication failed.